
Table of Contents
Understanding electricity is like understanding water flow - once you get it, everything clicks. Imagine voltage as water pressure, current as flow rate, resistance as a narrow pipe and power as how much work the flow performs. That mental image helps when you read wiring labels or compare appliance ratings. This guide explains the basic formulas electricians and hobbyists actually use: Ohm's Law (V = I × R) and the power formula (P = V × I). It also covers the difference between watts and volt‑amps, how utilities bill you in kWh, and practical rules people use to size breakers and estimate loads. You'll find real examples for US 120 V and EU 230 V homes plus a few historical lessons about what can go wrong if units are mixed up.
1Basic quantities and core formulas
Start with the three quantities everyone sees on labels: volts (V), amps (A), and ohms (Ω). Volts measure potential difference, amps measure current, and ohms measure resistance. Put them together with Ohm's Law and the power formula to solve most everyday questions about circuits.
Ohm's Law: V = I × R
Ohm's Law relates the three basic electrical quantities. If you know any two, you can find the third: V = I × R, I = V / R, R = V / I. Example: a 12 V source across a 6 Ω resistor yields I = 12 / 6 = 2 A. This simple relation is the backbone of circuit sizing and troubleshooting.
Power formula: P = V × I
Electrical power (watts) equals voltage times current: P = V × I. If the same 12 V circuit carries 2 A, it dissipates P = 12 × 2 = 24 W. For resistive loads you can also use P = I^2 × R or P = V^2 / R. These alternate forms come from substituting Ohm's Law into the power equation.
Units and common symbols
Quick reference: 1 W (watt) = 1 V × 1 A. Prefixes you'll see often: mA (milliamp, 10^-3 A), kW (kilowatt, 10^3 W). Be careful that kilowatt‑hour (kWh) measures energy (power × time), not instant power.
2Watts vs volt‑amps and power factor
In AC systems, apparent power (volt‑amps, VA) differs from real power (watts) because of phase shifts between voltage and current. Understanding that difference matters for sizing generators and UPS systems.
Real, apparent and reactive power
Real power (P, watts) does actual work or produces heat. Apparent power (S, VA) is the product of RMS voltage and current without accounting for phase. Reactive power (Q, vars) represents stored and returned energy in inductors and capacitors. Relationship: S^2 = P^2 + Q^2 and P = S × PF where PF is power factor.
Why power factor matters
Low power factor means higher current for the same real power, which increases losses and may require larger conductors or transformers. Utilities sometimes charge industrial customers for poor power factor. For most household devices (resistive loads) PF ≈ 1, but motors and fluorescent lights can have PF < 1.
Sizing UPS and generators
When you size a UPS or generator, use VA ratings but check the expected power factor. A 1000 VA UPS with PF 0.7 supplies about 700 W of real power. Always confirm PF on equipment nameplates or datasheets.
3Household standards and circuit basics
Homes around the world use different nominal voltages and wiring systems. Two common standards you'll meet are US nominal 120 V single‑phase and European nominal 230 V single‑phase. The difference changes how much current an appliance draws for the same power.
US 120 V vs EU 230 V: what it means for current
An appliance rated 1200 W draws 1200 / 120 = 10 A on a US 120 V supply, but 1200 / 230 ≈ 5.2 A on a 230 V supply. Higher voltage for the same power reduces current, which lets thinner wires carry the load and lowers I^2R losses.
Circuit breaker sizing and the 125% rule
Electricians often apply a 125% rule for continuous loads: breakers and conductors should be rated at least 125% of the continuous current. For example, a continuous 16 A load needs a breaker rated ≥ 20 A (16 × 1.25 = 20). Local codes vary, so always check national or regional wiring rules.
Appliance examples and real labels
Look at nameplates: a microwave might say 1200 W, 120 V; an EV charger could be 7 kW at 230 V. These labels let you compute current and pick the right breaker or cable. Remember start‑up currents on motors can be several times running current.
4Energy, kWh billing and simple calculations
Utilities bill energy in kilowatt‑hours (kWh). Knowing how to go from watts and hours to kWh helps you estimate monthly bills or compare energy use across appliances.
Convert watts to kWh
Energy (kWh) = Power (kW) × Time (h). Example: a 100 W bulb running 10 hours uses 0.1 kW × 10 h = 1.0 kWh. If electricity costs $0.15 per kWh, that bulb costs 1.0 × $0.15 = $0.15 for those 10 hours.
Estimating monthly bills
Add up appliance energies: fridge (150 W running average × 24 h × 30 d ≈ 108 kWh/month), lights, chargers, etc. Include standby loads. For big draws like heaters or EV chargers, multiply kW × hours of use to get kWh and then multiply by tariff to get cost.
Peak demand and time‑of‑use charges
Some tariffs include demand charges (based on peak kW used) or higher prices during peak hours. For businesses, reducing peak demand can cut bills significantly. Households with time‑of‑use tariffs benefit from shifting heavy loads to off‑peak times.
5Safety, common mistakes and historical lessons
Simple unit mistakes have led to big problems. Knowing common pitfalls, practical tricks and how professionals think about safety reduces errors in projects from DIY wiring to specifying equipment.
Famous mistake: Mars Climate Orbiter
You might remember the Mars Climate Orbiter (1999) loss linked to a units mix‑up: a thruster impulse was computed in pound‑seconds while the navigation team expected newton‑seconds. That mismatch caused trajectory errors. The lesson: always confirm units and interfaces between teams and tools.
Common mistakes hobbyists make
Mixing up VA and W, ignoring power factor, underestimating startup currents, and picking a breaker equal to the running current (instead of larger for safety) are frequent errors. Also, confusing watts (power) with kWh (energy) leads to wrong cost estimates.
Quick mental math and electrician tips
Handy tricks: at 120 V, multiply amps by 120 to get watts; at 230 V, multiply amps by 230. To estimate miles from km use ×0.62, and for electrical quick checks, round 230 to 240 for conservative sizing in many contexts. Electricians size continuous loads at 125% and allow motor start currents when choosing breakers.
Pro Tips
- 1Quick trick: P (W) = V × I (A). At 120 V multiply amps by 120 to get watts; at 230 V multiply by 230.
- 2For continuous loads multiply the operating current by 125% when selecting breaker and conductor sizes.
- 3To get energy in kWh: convert watts to kW (divide by 1000) then multiply by hours used.
- 4When sizing UPS or generator use VA rating and check power factor: W ≈ VA × PF.
- 5Watch for motor start currents; they can be several times running current and may trip undersized breakers.
Once you can move fluidly between V, I, R and P, many practical questions become simple arithmetic. Use Ohm's Law and P = V × I for quick checks, and remember the VA vs W distinction for AC systems. Try the related converters to test real appliance labels and billing scenarios. If you want hands‑on practice, plug appliance wattage into the watt‑to‑kW converter, compute daily kWh with hours of use, then multiply by your tariff to see the cost. Small changes in usage or voltage can change currents and wiring choices, so measure and calculate before you buy or install equipment.


